Where mist eliminators are used in ventilation systems

Five installation points — from the cooling coil to wet gas scrubbing

Four calculations to run before writing to a supplier

Each tool is a separate page with its formula, worked example and limits. All calculations run locally in your browser.

Comparison of the four site calculators. Numbers come only from your inputs.
ToolInputResultWhat it does not do
Airflow velocityQ, W, H (+ k_open)v_face, A_face; v_free with kdoes not replace the model datasheet velocity
Required sectionQ, v_target (± W or H)A_req, H_min / W_minnever inserts a “recommended velocity”
Pressure drop ΔPζ (from source), ρ, v_refΔP, Pano ζ — no result; invents no curves
Energy impact of ΔPQ, ΔP, hours, ηpower and energy/yeardoes not replace the electricity bill

The table scrolls horizontally on mobile.