Vane-type (blade) mist eliminators

Inertial deposition at channel bends — works only in horizontal flow

Anatomy of a vane packA pack of curved vanes: flow enters on the left, at channel bends droplets touch the walls and drain down into a gutter; droplet-free air leaves on the right.inlet: droplets in the streamoutlet: stream without visible dropletsa droplet follows the air while the bend is “gentle”film and droplets run down the channel wallAir phaseDroplet phase
Vane pack anatomy: channel bends, film, runoff into the drain pan

Schematic diagram, not an installation drawing.

A vane pack consists of profiled blades forming zigzag channels. Drops moving with the stream touch the walls by inertia at each channel turn, deposit, merge into a film and run downward into a drain pan with a separate outlet. The mechanism works only with correct orientation: the bends must “work” against the velocity vector, and the runoff must have a free path downward.

Typical applications

  • sections after cooling coils and humidifiers;
  • spray chambers at the duct outlet;
  • locations with a pressure drop constraint — provided ζ is confirmed by the data sheet.

What to check before selecting

  1. Orientation: a vertical pack, horizontal flow. Upward flow requires separate drainage solutions — check with the manufacturer.
  2. Drainage: a free path for the film into the pan; breaks and horizontal runoff sections are not acceptable without a calculation.
  3. Velocity: check the operating v_face with the “Airflow velocity” tool; the allowable velocity comes only from the model data sheet.
  4. Service: access for inspection and washing.

What the manufacturer must state

This table is not a spec sheet: without the specific model datasheet, values stay “no data”. No typical numbers are ever substituted.

Values the manufacturer must state; without a document — “no data”.
ParameterValueStatus
Efficiency at a given droplet load—per the model data sheet
Maximum velocity (re-entrainment onset)—per the model data sheet
Pressure drop ΔP at the operating velocity—per the model data sheet
Vane pitch and profile, pack depth—depends on the model

The table scrolls horizontally on mobile.

Face and free areaRectangle of the W × H section; the free area A_free = A_face × k_open is shown dashed.W, mmH, mmA_face = W × H — the whole face areaA_free = A_face × k_open — air passagek_open depends on the profile and pitch of a specificmodel — there is no universal value.