Engineering atlas of mist eliminators

Separate drops from the stream — before they escape into the system

Constructive families, applicability conditions, preliminary calculations and a datasheet questionnaire for the manufacturer. No datasheet promises — only verifiable engineering logic.

  • 01Check the air velocity in the section — in 30 seconds
  • 02Compare 4 constructive families by conditions, not by advertising
  • 03Assemble the questionnaire and pass it to your supplier
Droplet separation principle: flow through vanes, droplets to the drainDiagram: a humid stream passes left-to-right through a vane pack; droplets deposit at channel bends and drain into a pan with a separate outlet; droplet-free air leaves on the right.Duct / casingHumid stream, m/svanesDroplet-free streamGravity flow to the pan — separate outletair · droplets: deposit → drain

Schematic diagram, not an installation drawing.

Airflow velocity in the section

Decimal separator — dot or comma. Values are positive.

Free-area ratio — from the model datasheet or your project. It is never filled in automatically.

—m/s
A_face = — м²formulayour input

The result appears after a correct input. Worked example: Q=7200, W=1000, H=500 → 4 m/s; with k=0.8 → v_free = 5 m/s.

Face and free areaRectangle of the W × H section; the free area A_free = A_face × k_open is shown dashed.W, mmH, mmA_face = W × H — the whole face areaA_free = A_face × k_open — air passagek_open depends on the profile and pitch of a specificmodel — there is no universal value.

Constructive catalog

Four constructive families

Each row is a class of construction: the separation principle, where it applies, and what to verify before choosing. Datasheet figures are never replaced by typical numbers.

Where they are installed

Installation points for mist eliminators

The place in the system defines the duty: after a cooling coil, a humidifier, a spray chamber, at the air intake, or in wet gas scrubbing.

All installation points →

Calculators

Four calculations to run before writing to a supplier

Each tool is a separate page with its formula, worked example and limits. All calculations run locally in your browser.

Comparison of the four site calculators. Numbers come only from your inputs.
ToolInputResultWhat it does not do
Airflow velocityQ, W, H (+ k_open)v_face, A_face; v_free with kdoes not replace the model datasheet velocity
Required sectionQ, v_target (± W or H)A_req, H_min / W_minnever inserts a “recommended velocity”
Pressure drop ΔPζ (from source), ρ, v_refΔP, Pano ζ — no result; invents no curves
Energy impact of ΔPQ, ΔP, hours, ηpower and energy/yeardoes not replace the electricity bill

The table scrolls horizontally on mobile.

Engineer’s route

Problem → principle → type → calculation → limits → questionnaire

Problem → principle → type → calculation → limits → questionnaireDiagram of the selection route: from problem to questionnaireProblem:dropletcarryoverDuty andinstallationpointConstructivefamilyQuestionnaire

Handbook

Short answers to common questions

The whole handbook →

The site is not a shop and not a product data sheet: it is an engineering atlas. It helps you follow the route “problem → mist separation principle → design type → calculation → constraint check → questionnaire” and prepare a correct request to a manufacturer. All calculations run locally in your browser; numerical characteristics of specific models are deliberately not published — their place is the manufacturer documentation.